Products Downloads Condensate discharge Condensate processing Filtration Drying Process technologyBEKOBLIZZ Benefits Download Function Payback analysis Reasons Technical Data BEKOBLIZZ LC BEKOKAT Distribution Measurement Service Training Tools
 
 

Compressed air deep-freezing system

BEKOBLIZZ Power supply Compr. air connection Order Reference Price
120-W1-35 3x400V/50Hz 1" 4000 411 All prices on request
240-W2-35 3x400V/50Hz 1½" 4000 539
410-W2-35 3x400V/50Hz 1½" 4000 354
270-W2-45 3x400V/50Hz 1½" 4000 242
410-W2-45 3x400V/50Hz 1½" 4000 545

Specification

  *1) *1)       *2)    
  Max.
vol.-flow
at intake
Max.
vol.-flow
at outlet
compressed
air outlet
temperature
Max.
operating
pressure
Electrical
power
consumption
Cooling-
water
consumption
Dimension
(h/d/w)
Weight
BEKOBLIZZ m³/h
(scfm)
m³/h
(scfm)
°C
(°F)
bar
(psi)
kW
(HP)
m³/h
(scfm)
mm
(inches)
kg
(lbs)
016-N2-25 16*3)
(9)
16
(9)
-25
(-13)
350
(5076)
1.3
(1.8)
0.5
(0.29)
1000/1000/640
(39.4/39.4/25.2)
225
(496)
120-W1-35 145
(85)
120
(71)
-35
(-31)
16
(232)
2.5
(3.35)
0.54
(0.32)
1610/994/974
(63.4/39.1/38.3)
700
(1543)
240-W2-35 290
(171)
240
(145)
-35
(-31)
16
(232)
4.5
(6.0)
1.10
(0.65)
1850/1420/1220
(72.8/55/40.4)
1300
(2866)
410-W2-35 495
(291)
410
(241)
-35
(-31)
16
(232)
6.6
(8.9)
1.63
(0.96)
1850/1510/1340
(72.8/59.4/40.4)
1380
(3042)
270-W2-45 338
(199)
270
(159)
-45
(-49)
16
(232)
7.3
(9.7)
1.37
(0.81)
1850/1460/1220
(72.8/59.4/40.4)
1430
(3153)
410-W2-45 513
(302)
410
(241)
-45
(-49)
16
(232)
9.8
(13.1)
2.17
(1.28)
1850/1510/1340
(72.8/59.4/40.4)
1480
(3263)

Other sizes and power supplies on request
Other outlet temperatures on request
Design data:
Pressure: 7 bar (102 psi)
Power supply: 400 V / 3ph / 50 Hz
Compressed air temperature (intake): + 35°C
Compressed air quality (intake): also oil-containing and 100% saturated compressed air
Noise level: <65dB (A)
Pressure vessel: TÜV-approved for alternating pressure operation

*1) Air volume flows based on +20°C ( +68°F) and 1 bar (14.5 psi) abs.
*2) Cooling water consumption based on intake temperature +20°C (+68°F)